Siemens SINAMICS S Series - p9355 SI motion transition time STOP F to STOP B (Motor Module); SI Mtn t F�>B MM; p9356 SI motion pulse cancelation delay time (Motor Module); SI Mtn IL t_del MM; p9357 SI motion pulse cancelation test time (Motor Module); SI Mtn IL t MM; p9358 SI motion acceptance test mode time limit (Motor Module); SI Mtn acc t MM

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-983
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the transition time from STOP F to STOP B.
Dependency: Refer to: C01711
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
Description: Sets the delay time for the safe pulse cancelation after STOP B / SS1.
Dependency: Refer to: p9360, p9556
Refer to: C01701
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
SS1: Safe Stop 1
Description: Sets the time after which the pulses must have been canceled when initiating the test stop.
Dependency: Refer to: p9557
Refer to: C01798
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note: A change only becomes effective after a POWER ON.
Description: Sets the maximum time for the acceptance test mode.
If the acceptance test mode takes longer than the selected time limit, then the mode is automatically terminated.
Dependency: Refer to: p9558
Refer to: C01799
p9355 SI motion transition time STOP F to STOP B (Motor Module) / SI Mtn t F->B MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2825
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 0.00 [µs]
p9356 SI motion pulse cancelation delay time (Motor Module) / SI Mtn IL t_del MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2825
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 600000000.00 [µs] 100000.00 [µs]
p9357 SI motion pulse cancelation test time (Motor Module) / SI Mtn IL t MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 10000000.00 [µs] 100000.00 [µs]
p9358 SI motion acceptance test mode time limit (Motor Module) / SI Mtn acc t MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
5000000.00 [µs] 100000000.00 [µs] 40000000.00 [µs]