Siemens SINAMICS S Series - p1911 Number of phases to be identified; Qty ph to ident; r1912 Stator resistance identified; R_stator ident; r1912[0...2] Identified stator resistance; R_stator ident

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-496
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: "Quick commissioning" must be carried out (p0010 = 1) before executing the motor data identification routine!
In the simulation mode, the parameter cannot be written into. When selecting the motor data identification routine,
the drive data set changeover is suppressed.
Refer to: p1272, p1900
Caution: After the motor data identification (p1910 > 0) has been selected, alarm A07991 is output and a motor data identifi-
cation routine is carried out as follows at the next power-on command:
- current flows through the motor and a voltage is present at the drive converter output terminals.
- during the identification routine, the motor shaft can rotate through a maximum of half a revolution.
- however, no torque torque is generated.
Notice: In order to permanently accept the determined settings they must be saved in a non-volatile fashion (p0971,
p0977).
Note: When setting p1910, the following should be observed:
1. "With transfer" means:
The parameters specified in the description are overwritten with the identified values and therefore have an influ-
ence on the controller setting.
2. "Without transfer" means:
The identified parameters are only displayed in the range r1912 ... r1926. The controller settings remain
unchanged.
Description: Sets the number of phases to be identified.
Values: 1: 1 phase U
2: 2 phases U, V
3: 3 phases U, V, W
Note: When identifying with several phases, the accuracy increases and also the time it takes to make the measurement.
Description: Displays the identified stator resistance.
Dependency: Refer to: p1909, p1910, r1913, r1915, r1925, r1927, r1932, r1933, r1934, r1935, r1936, r1950, r1951, p1952,
p1953
Description: Displays the identified stator resistance.
p1911 Number of phases to be identified / Qty ph to ident
VECTOR Can be changed: T Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 3 1
r1912 Stator resistance identified / R_stator ident
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Ohm] - [Ohm] - [Ohm]
r1912[0...2] Identified stator resistance / R_stator ident
VECTOR Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Ohm] - [Ohm] - [Ohm]