Remedy: - for a flying changeover between operation with and without encoder with pole position identification after POWER
ON or commissioning (p0010 not equal to zero) enable the pulses once at zero speed. This means that the pole
position identification routine is carried out and the result is available for operation.
- carry out the EDS changeover with the pulses inhibited, or, before the changeover, carry out a pole position iden-
tification using this data set.
A07998 Drive: Motor data identification active on another drive
Drive object: SERVO
Reaction: NONE
Acknowledge: NONE
Cause: The motor data identification is activated on the drive object specified in the fault value and interlocks the other drive
objects so they cannot be powered-up.
Fault value (r0949, interpret decimal):
Drive object with the active motor data identification.
See also: p1910 (Motor data identification routine, stationary (standstill)), p1960 (Rotating measurement selection)
Remedy: - wait for the complete execution of the motor data identification of the drive object designated in the fault value.
- de-select the motor data identification for the drive object designated in the fault value (p1910 = 0 or p1960 = 0).
A07999 Drive: Motor data identification cannot be activated
Drive object: SERVO
Reaction: NONE
Acknowledge: NONE
Cause: Closed-loop control is enabled on a SERVO drive object type. To select motor data identification, pulses must be
canceled for all SERVO drive objects.
Fault value (r0949, interpret decimal):
Drive object with enabled closed-loop control.
Remedy: Withdraw the pulse enable on all drives and re-activate the motor data identification.
F08000 (N, A) TB: +/-15 V power supply faulted
Drive object: All objects
Reaction: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Terminal Board 30 detects an incorrect internal power supply voltage.
Fault value (r0949, interpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy: - replace Terminal Board 30.
- replace Control Unit.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F08010 (N, A) TB: Analog-digital converter
Drive object: All objects
Reaction: A_INFEED: NONE (OFF1, OFF2)
SERVO: NONE (IASC / DCBRAKE, OFF1, OFF2, OFF3, STOP1, STOP2)
VECTOR: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3, STOP1, STOP2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The analog/digital converter on Terminal Board 30 has not supplied any converted data.
Remedy: - check the power supply.
- replace Terminal Board 30.