Parameters
List of parameters
1-44
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the control word for the Basic Operator Panel (BOP).
Description: Displays the actual, smoothed speed setpoint at the input of the speed controller or V/f characteristic (after the inter-
polator).
Dependency: Refer to: r0060
Note: Smoothing time constant = 100 ms
The signal is not suitable as process quantity and may only be used as display quantity.
The speed setpoint is available smoothed (r0020) and unsmoothed (r0060).
Description: Displays the actual, smoothed velocity setpoint at the input of the velocity controller or V/f characteristic (after the
interpolator).
Dependency: Refer to: r0060
Note: Smoothing time constant = 100 ms
The signal is not suitable as process quantity and may only be used as display quantity.
The velocity setpoint is available smoothed (r0020) and unsmoothed (r0060).
r0019.0...14 CO/BO: Control word BOP / STW BOP
CU_S Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON / OFF (OFF1) ON OFF (OFF1) -
01 No coast-down / coast-down (OFF2) No coast down Coast down (OFF2) -
02 No Quick Stop / Quick Stop (OFF3) No Quick Stop Quick Stop (OFF3) -
07 Acknowledge fault (0 -> 1) Yes No -
13 Motorized potentiometer raise Yes No -
14 Motorized potentiometer lower Yes No -
r0020 Speed setpoint smoothed / n_set smth
SERVO, VECTOR Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 5020, 6799
P-Group: Displays, signals Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r0020 Velocity setpoint smoothed / v_set smth
SERVO (Lin) Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 5020, 6799
P-Group: Displays, signals Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]