Siemens SINAMICS S Series - p1909[0...n] Motor data identification control word; MotID STW

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-494
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p1910, r1912, r1913, r1915, r1925, r1927, r1932, r1933, r1934, r1935, r1936, r1950, r1951, p1952, p1953
Note: For an induction motor (ASM), the following bits are effective: 8, 9, 10, 13
For a synchronous motor (SRM), the following bits are effective: 8, 9, 13, 14
Re bit 14:
- after successfully determining the voltage emulation error, the display of the phase voltage actual values r0089
and the active power actual value r0082 and the torque actual value r0080 are significantly more accurate.
- the voltage emulation errors should be identified with the Motor Module in the warm state.
- the motor temperature (r0035) should not change significantly (i.e. it should not be identified immediately after a
load duty cycle).
Description: Sets the configuration of the motor data identification.
Note: Note for PEM:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature induc-
tance Lq are measured at a low current.
When de-selecting with bit 11 or in the V/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
Bit field: Bit Signal name 1 signal 0 signal FP
08 Measure D inductance Yes No -
09 Measure Q inductance Yes No -
10 Magnetizing field inductance and measure
rotor resistance
Yes No -
13 Measure commutation angle and direction
of rotation
Yes No -
14 Determining the voltage emulation error Yes No -
p1909[0...n] Motor data identification control word / MotID STW
VECTOR Can be changed: T Calculated: CALC_MOD_ALL Access level: 3
Data type: Unsigned16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor identification Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Stator inductance estimate no measure-
ment
Yes No -
01 Cl.-loop current control w/ dead-beat con-
troller
Yes No -
02 Rotor time constant estimate no measure-
ment
Yes No -
03 Leakage inductance estimate no measure-
ment
Yes No -
04 Activates the identification dynamic leak-
age inductance
Yes No -
05 Determine Tr and Lsig evaluation in the time
range
Yes No -
06 Activates vibration damping Yes No -
07 De-activates the vibration detection Yes No -
11 De-activate pulse measurement Lq Ld Yes No -
12 De-activate rotor resistance Rr measure-
ment
Yes No -
15 Only measure stator resistance and valve
voltage error
Yes No -