Parameters
List of parameters
1-212
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p0604, p0605
Refer to: F07011, A07910
Note: With p0606 = 0 s, the timer stage is de-activated and only the fault threshold is effective.
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC sensor: The timer minimum value has no particular significance.
Description: Sets the timer stage between the output of alarm and fault for a temperature sensor fault.
If there is a sensor fault, this timer stage is started. If the sensor fault is still present after the timer stage has
expired, a corresponding fault message is output.
Note: If the motor is an induction motor, the timer is switched off when setting the minimum value and no alarm is output.
Temperature monitoring is then based on the thermal model.
Description: Sets the system response when the motor temperature reaches the alarm threshold.
Values: 0: No response only alarm no reduction of I_max
1: Alarm with reduction of I_max and fault
2: Alarm and fault no reduction of I_max
Dependency: Refer to: p0601, p0604, p0605
Refer to: F07011, A07910
Note: the I_max reduction is not executed for PTC (p0601 = 1).
The I_max reduction results in a lower output frequency.
Description: Sets the alarm threshold 1 for monitoring the motor temperature.
Note: The alarm threshold is not, as for p0604, coupled to the timer p0606.
p0607[0...n] Temperature sensor fault timer / Sensor fault time
SERVO, VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 0.100 [s]
p0610[0...n] Motor overtemperature response / Mot temp response
VECTOR Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 1
p0616[0...n] Motor overtemperature alarm threshold 1 / Mot temp alarm 1
SERVO Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 195.0 [°C]