List of parameters
Parameters
1-441
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the internally converted factor to interconnect to the scaling of the torque/force limits.
Dependency: Refer to: p1528, p1529, p1542, p1544, p1545
Description: Sets the evaluation for the torque/force reduction when traversing to a fixed stop.
Dependency: Refer to: p1528, p1529, p1542, r1543, p1545
Note: 4000 hex (16384 dec) in the MOMRED control word corresponds to a reduction by the percentage specified in this
parameter.
Description: Sets the evaluation for the torque/force reduction when traversing to a fixed stop.
Dependency: Refer to: p1528, p1529, p1542, r1543, p1545
Note: 4000 hex (16384 dec) in the MOMRED control word corresponds to a reduction by the percentage specified in this
parameter.
Description: Sets the signal source to activate/de-activate the "travel to fixed stop" function
1: Travel to fixed stop is active
0: Travel to fixed stop is inactive
Dependency: Refer to: p1542, r1543, p1544
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: When traveling to fixed stop, the fault F07900 "motor blocked" is suppressed.
When the function module "position positioner" (r0108.4 = 1) is activated, this binector input is interconnected as
follows as standard:
BI: p1545 = r2683.14
r1543 CO: Travel to fixed stop force scaling / TfS F scal
SERVO (Lin) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5610
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1544 Travel to fixed stop evaluation, torque reduction / TfS M_red eval
SERVO Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5610
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [%] 65535 [%] 100 [%]
p1544 Travel to fixed stop evaluation force reduction / TfS F_red eval
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5610
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [%] 65535 [%] 100 [%]
p1545[0...n] BI: Activates travel to a fixed stop / TfS activation
SERVO Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2520, 3617
P-Group: Commands Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 0