Parameters
List of parameters
1-728
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the hysteresis for the alarm threshold of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Description: Sets the hysteresis for the alarm threshold of the VSM to monitor the line filter temperature.
Dependency: Refer to: p3667
Description: Sets CT gain of the CT connected at the 10 V input of the Voltage Sensing Module (VSM).
The parameter specifies the current magnitude in [A] referred to the input voltage at the VSM in [V].
Example:
CT with 1 V per 200 A.
--> p3670 = 200
Dependency: Refer to: r3671, r3672
Note: The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
Description: Sets CT gain of the CT connected at the 10 V input of the Voltage Sensing Module (VSM).
The parameter specifies the current magnitude in [A] referred to the input voltage at the VSM in [V].
Example:
CT with 1 V per 200 A.
--> p3670 = 200
Dependency: Refer to: r3671, r3672
p3669 VSM line filter overtemperature hysteresis / VSM filt_T hyst
A_INF, S_INF Can be changed: T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 9886
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1.0 [K] 50.0 [K] 3.0 [K]
p3669[0...n] VSM line filter overtemperature hysteresis / VSM filt_T hyst
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9886
P-Group: - Units group: 21_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
1.00 [K] 50.00 [K] 3.00 [K]
p3670 VSM 10 V input CT gain / VSM CT_gain
A_INF, S_INF Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [A] 1000.000 [A] 1.000 [A]
p3670[0...n] VSM 10 V input CT gain / VSM CT_gain
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [A] 1000.000 [A] 1.000 [A]

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S Series and is the answer not in the manual?

Siemens SINAMICS S Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals