Description: Sets the normalization characteristic for the analog input of terminal module 41 (TM41).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X523.1/X523.2)
Note: The parameters for the characteristic do not limit.
Description: Sets the response threshold for wire-breakage monitoring of the analog inputs of terminal module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The wire breakage monitoring is active for the following type of analog input: p4056[x] = 3 (current input unipolar,
monitored 4 mA ... 20 mA).
Refer to: r4056, p4056
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on terminal module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Board 30 (TB30).
The offset is added to the input signal before the normalization characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
p4060[0...0] TM41 analog input, characteristic value y2 / TM41 AI char y2
TM41 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4061[0...1] TM31 analog inputs, wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [mA] 20.00 [mA] 2.00 [mA]
p4062[0...1] TM31 analog inputs, wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p4063[0...1] TB30 analog inputs offset / TB30 AI offset
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 0.000 [V]