Siemens SINAMICS S Series - p4060[0...0] TM41 analog input, characteristic value y2; TM41 AI char y2; p4061[0...1] TM31 analog inputs, wire breakage monitoring response threshold; TM31 WireBrkThresh; p4062[0...1] TM31 analog inputs, wire breakage monitoring delay time; TM31 wirebrk t_del; p4063[0...1] TB30 analog inputs offset; TB30 AI offset

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of parameters
Parameters
1-801
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the normalization characteristic for the analog input of terminal module 41 (TM41).
The normalization characteristic for the analog inputs is defined using two points.
This parameter specifies the y coordinate (percentage) of the 2nd value pair of the characteristic.
Index: [0] = AI 0 (X523.1/X523.2)
Note: The parameters for the characteristic do not limit.
Description: Sets the response threshold for wire-breakage monitoring of the analog inputs of terminal module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The wire breakage monitoring is active for the following type of analog input: p4056[x] = 3 (current input unipolar,
monitored 4 mA ... 20 mA).
Refer to: r4056, p4056
Description: Sets the delay time for wire-breakage monitoring of the analog inputs on terminal module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Description: Sets the offset for the analog inputs of Terminal Board 30 (TB30).
The offset is added to the input signal before the normalization characteristic.
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
p4060[0...0] TM41 analog input, characteristic value y2 / TM41 AI char y2
TM41 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-1000.00 [%] 1000.00 [%] 100.00 [%]
p4061[0...1] TM31 analog inputs, wire breakage monitoring response threshold /
TM31 WireBrkThresh
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [mA] 20.00 [mA] 2.00 [mA]
p4062[0...1] TM31 analog inputs, wire breakage monitoring delay time / TM31 wirebrk t_del
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p4063[0...1] TB30 analog inputs offset / TB30 AI offset
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
-20.000 [V] 20.000 [V] 0.000 [V]