List of parameters
Parameters
1-31
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Operating display for the drive.
Values: 0: [00] Operation - everything enabled
10: [10] Operation - set "enable setpoint" = "1" (p1142, p1152)
11: [11] Operation - set "enable speed controller" = "1" (p0856)
12: [12] Operation - RFG frozen, set "RFG start" = "1" (p1141)
13: [13] Operation - set "enable RFG" = "1" (p1140)
14: [14] Oper. - MotID, excit. running and/or brake opens, SS2, SOS
15: [15] Operation - open brake (p1215)
16: [16] Oper - withdraw braking w/ OFF1 using "ON/OFF1" = "1"
17: [17] Oper - braking w/ OFF3 can only be interrupted w/ OFF2
18: [18] Operation - brake on fault remove fault acknowledge
19: [19] Operation - armature short-circuit active (p1230, p1231)
21: [21] Ready - set "enable operation" = "1" (p0852)
22: [22] Ready - de-magnetization running (p0347)
23: [23] Ready - set "infeed operation" = "1" (p0864)
31: [31] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41: [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840)
42: [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845)
43: [43] Power-on inhibit - set "OC/OFF3" = "1" (p0848, p0849)
44: [44] Power-on inhibit - connect 24 V to terminal EP (hardware)
45: [45] Power-on inhib - remove fault cause, acknowledge fault
46: [46] Power-on inhibit - exit comm mode (p0009, p0010)
60: [60] Infeed de-activated/not operational
250: [250] Device signals a topology error
Dependency: Refer to: r0046
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
SOS: Safe Operating Stop
Description: Operating display for the infeed.
Values: 0: [00] Operation - everything enabled
31: [31] Rdy to power-up - pre-chrg running (p0857)
32: [32] Ready to power-up - set "ON/OFF1" = "0/1" (p0840)
41: [41] Power-on inhibit - set "ON/OFF1" = "0" (p0840)
42: [42] Power-on inhibit - set "OC/OFF2" = "1" (p0844, p0845)
44: [44] Power-on inhibit - connect 24 V to terminal EP (hardware)
45: [45] Power-on inhib - remove fault cause, acknowledge fault
r0002 Drive operating display / Drv op_display
SERVO, VECTOR Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 250 -
r0002 Infeed operating display / INF op_display
B_INF Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 250 -