Parameters
List of parameters
1-318
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description: Displays the speed/velocity setpoint after the changeover and limiting the direction.
Description: Sets the ramp-function generator type.
Values: 0: Single ramp-function generator
1: Extended ramp-function generator
Note: Another ramp-function generator type can only be selected when the motor is at a standstill.
Description: Displays the setpoint at the input of the ramp-function generator.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The setpoint is influenced by other functions, e.g. skip (suppressed) speeds, minimum and maximum limits.
r1114 CO: Setpoint after the direction of rotation limit / Setp after limit
SERVO (Extended
setp), VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1550, 3040,
3050
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]
r1114 CO: Setpoint after the direction limiting / Setp after limit
SERVO (Extended
setp, Lin)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1550, 3040,
3050
P-Group: Setpoints Units group: 4_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [m/min] - [m/min] - [m/min]
p1115 Ramp-function generator selection / RFG selection
SERVO (Extended
setp), VECTOR
Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: 1550, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0
r1119 CO: Ramp-function generator setpoint at the input / RFG setp at inp
SERVO (Extended
setp), VECTOR
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 1550, 1750,
3050, 3060, 3070, 8010
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [RPM] - [RPM] - [RPM]