Figure 2-260 9552 – Digital inputs, electrically isolated (DI 4 ... DI 7)
- 9552 -
Function diagram
87654321
fp_9552_51_eng.vsd
SINAMICS
21.07.04 V02.05.00
Terminal Module 31 (TM31) - Digital inputs, electrically isolated (DI 4 ... DI 7)
DI4
1
1 = Simulation on
p4095.4
r4023.4
r4023.5
r4023.6
r4023.7
DI5
1
p4095.5
DI 6
1
p4095.6
DI 7
1
p4095.7
p4096.7
p4096.6
p4096.5
p4096.4
24 V
5 V
1
0
1
0
1
0
1
0
X524.M
X524.+
+
X530.1
X530.2
X530.3
X530.4
+24 V
M
r4021.4
r4021.5
r4021.6
r4021.7
p4099[0] (4000.00 µs)
DO: TM31
X524.M
X530.5
M2
M
X530.6
X524.+
M
24 V DC to the next device
<1>
+
<1>
When using the electrical isolation, omit the
terminal jumper and connect the load power supply
shown as a dashed line.
<1>
24 V
+24 V
r4022
TM31 DI status
r4023
TM31 DI status inv
DI 4 (X530.1)
r4022.4
DI 5 (X530.2)
r4022.5
DI 6 (X530.3)
r4022.6
DI 7 (X530.4)
r4022.7