Parameters
List of parameters
1-444
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source to change over the torque limits between variable and fixed torque limit.
1 signal from BI: p1551:
The variable torque limit applies (fixed torque limit + scaling).
0 signal from BI: p1551:
The fixed torque limit applies.
Example:
In order that for a Quick Stop (OFF3) the fixed torque limit is effective, BI: p1551 must be interconnected to r0899.5.
Description: Sets the signal source to change over the force limits between variable and fixed force limit.
1 signal from BI: p1551:
The variable force limit applies (fixed force limit + scaling).
0 signal from BI: p1551:
The fixed force limit applies.
Example:
In order that for a Quick Stop (OFF3) the fixed force limit is effective, BI: p1551 must be interconnected to r0899.5.
Description: Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
Description: Sets the signal source for the scaling of the upper force limiting to limit the velocity controller output without taking
into account the current and power limits.
p1551[0...n] BI: Torque limit variable/fixed signal source / M_lim var/fixS_src
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 5620, 5630,
6060, 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1
p1551[0...n] BI: Force limit variable/fixed signal source / F_lim var/fixS_src
SERVO (Lin) Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 5620, 5630,
6060, 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1
p1552[0...n] CI: Torque limit upper scaling without offset / M_max up offs scal
SERVO, VECTOR
(n/M)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6060
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1
p1552[0...n] CI: Force limit upper scaling without offset / F_max up offs scal
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6060
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1