Parameters
List of parameters
1-482
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the proportional gain for the Rs adaptation of the motor model for an induction motor (ASM).
Description: Sets the proportional gain for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Sets the integral time for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Displays the corrective value for the Lh adaptation of the motor model for an induction motor (ASM).
Description: Displays the power-on stator frequency for the Rs adaptation for the induction motor (ASM).
p1783[0...n] Motor model Rs adaptation Kp / MotMod Rs Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0.000 1.000 0.100
p1785[0...n] Motor model Lh adaptation Kp / MotMod Lh Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
0.000 1.000 0.100
p1786[0...n] Motor model Lh adaptation integral time / MotMod Lh Tn
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
10 [ms] 10000 [ms] 100 [ms]
r1787[0...n] Motor model Lh adaptation corrective value / MotMod Lh corr
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]
r1789 Motor model Rs adaptation switch-in frequency / MotMod Rs f_on
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]