Parameters
List of parameters
1-252
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 10 = 0: No master control by PLC
Bit 10 = 1: Master control by PLC
This bit is used to initiate a response for the drives when the control fails (F07220). If there is not control available,
then BI: p0854 should be set to a 1 signal.
Description: Sets the signal source for the command "unconditionally open holding brake".
Dependency: Refer to: p0858
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (uncondition-
ally open holding brake).
Description: Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency: Refer to: r0898
Note: If "enable speed controller" is withdrawn, then if a brake being used, then it is closed.
If "speed controller enable" is withdrawn, the pulses are not canceled.
Description: Sets the signal source for the command "enable speed controller" (r0898.12).
0 signal: Set the I component and speed controller output to zero.
1 signal: Enable speed controller.
Dependency: Refer to: r0898
Note: If "enable speed controller" is withdrawn, then if a brake being used, then it is closed.
If "speed controller enable" is withdrawn, the pulses are not canceled.
p0855[0...n] BI: Unconditionally release holding brake / Uncond open brake
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501, 2701,
2707
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0856[0...n] BI: Enable speed controller / Enable n_ctrl
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501, 2701,
2707
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p0856[0...n] BI: Enable velocity controller / Enable v_ctrl
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501, 2701,
2707
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1