Parameters
List of parameters
1-322
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note: This time can be exceeded if the DC-link voltage reaches its maximum value.
Description: Sets the initial rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the final rounding-off time for OFF3 for the extended ramp generator.
Description: Sets the signal source for control word 1 bit 4 (operating condition/disable ramp-function generator).
Dependency: Refer to: p1141, p1142
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 4 = 0: Inhibits the ramp-function generator (the ramp-function generator output is set to zero)
Bit 4 = 1: Operating condition (the ramp-function generator can be enabled)
Description: Sets the signal source for control word 1 bit 4 (operating condition/disable ramp-function generator).
p1135[0...n] OFF3 ramp-down time / RFG OFF3 t_ramp-dn
VECTOR Can be changed: C2(1), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3060, 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 3.000 [s]
p1136[0...n] OFF3 initial rounding-off time / RFGOFF3 t_strt_rnd
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3070, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1137[0...n] OFF3 final rounding-off time / RFG OFF3 t_end_del
SERVO (Extended
setp), VECTOR
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 3070
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 30.000 [s] 0.000 [s]
p1140[0...n] BI: Enables the ramp-function generator / Enable RFG
SERVO, VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2442, 2443,
2501
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p1140 BI: Enables the ramp-function generator / Enable RFG
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1