List of parameters
Parameters
1-261
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: Re bit 0, 1, 2, 4, 5, 6, 9:
For PROFIdrive, these signals are used for status word 1.
Re bit 13:
When the "Safe Brake Control" (SBC) is activated and selected, the brake is no longer controlled using this signal.
Re bit 14, 15:
These signals are only of significance when the "extended brake control" function module is activated (r0108.14 =
1).
Description: Displays the status word of the sequence control.
Note: Re bit 0, 1, 2, 6:
For PROFIdrive, these signals are used for status word 1.
r0899.0...15 CO/BO: Status word sequence control / ZSW seq_ctrl
TM41 Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 9680
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ready to power up Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
04 Coast down active No Yes -
05 Quick Stop active No Yes -
06 Power-on inhibit Yes No -
09 Control requested Yes No -
13 Zero mark enabled Yes No -
14 Track A/B enabled Yes No -
15 Interface encoder emulation enabled Yes No -