List of parameters
Parameters
1-459
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the output of the excitation current monitoring for separately excited synchronous motors.
Description: Sets the signal source for the individual feedback signals from the excitation.
Index: [0] = Excitation ready to be powered-up
[1] = Excitation ready
[2] = Excitation operational
[3] = Excitation group signal fault
[4] = Excitation, group signal alarm
[5] = Not used
[6] = Not used
Dependency: Refer to: r1649
Description: Sets the monitoring time of the excitation.
After an ON command, the feedback signal must be received within this monitoring time.
Note: After the on command for the excitation (r1648.0 = 1), its feedback signal must be available at r1649.1 within this
monitoring time (BI: p1645[1]).
The same monitoring time is effective after the excitation is enabled for operation (r1648.3 = 1) up to the feedback
signal "excitation in operation" (r1649.2 = 1, BI: p1645[2]).
Description: Sets the switch-off delay time to shut-down the excitation equipment.
Note: The delay time starts if, when powering-down, r0863.0 = 0.
r1648.0 and r1648.3 are reset at the end of the delay time.
r1644 Excitation current monitoring output / I_exc_monit outp
VECTOR (n/M) Can be changed: - Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: 6727
P-Group: Closed-loop control Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1645[0...6] BI: Excitation feedback signals signal source / Exc FS S_src
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 6495
P-Group: Commands Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
- - 1
p1646 Excitation monitoring time / Excit t_monit
VECTOR (n/M) Can be changed: T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 6495
P-Group: Commands Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
2.0 [s] 1300.0 [s] 20.0 [s]
p1647 Excitation switch-out delay time / Exc t_off
VECTOR (n/M) Can be changed: T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 6495
P-Group: Commands Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.5 [s] 5.0 [s] 0.8 [s]