List of parameters
Parameters
1-211
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Description: Sets the fault threshold to monitor the motor temperature.
Caution: This parameter is automatically preset for motors from the motor list (p0301). When selecting a catalog motor, this
parameter cannot be changed (write protection). Information in p0300 should be carefully observed when removing
write protection.
Note: The parameter is automatically preset for motors from the motor list (p0301).
Description: Sets the timer stage for the alarm threshold for the motor temperature monitoring function.
This timer stage is started when the temperature alarm threshold (p0604) is exceeded.
If the timer stage expires before the temperature in the meantime falls below the alarm threshold, the fault F07011
is output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer stage has expired, then fault
F07011 is immediately output. As long as the motor temperature has still not exceeded the fault threshold and the
alarm thresholds have again been fallen below, the fault can be acknowledged.
Dependency: Refer to: p0604, p0605
Refer to: F07011, A07910
Note: With p0606 = 0 s, the timer stage is de-activated and only the fault threshold is effective.
KTY sensor: When setting the minimum value, the timer is disabled and a fault is not output until p0605 is
exceeded.
PTC sensor: The timer minimum value has no particular significance.
Description: Sets the timer stage for the alarm threshold for the motor temperature monitoring function.
This timer stage is started when the temperature alarm threshold (p0604) is exceeded.
If the timer stage expires before the temperature in the meantime falls below the alarm threshold, the fault F07011
is output.
If the temperature fault threshold (p0605) is prematurely exceeded before the timer stage has expired, then fault
F07011 is immediately output. As long as the motor temperature has still not exceeded the fault threshold and the
alarm thresholds have again been fallen below, the fault can be acknowledged.
p0605[0...n] Motor overtemperature fault threshold / MotTempFaultThresh
SERVO, VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 145.0 [°C]
p0606[0...n] Motor overtemperature timer / Mot TempTimeStage
SERVO Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 240.000 [s]
p0606[0...n] Motor overtemperature timer / Mot TempTimeStage
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 600.000 [s] 0.000 [s]