List of parameters
Parameters
1-69
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: The maximum output current is determined by the parameterized current limit and the motor and converter thermal
protection.
Refer to: p0290, p0640
Description: Displays actual absolute current.
Dependency: Refer to: r0027
Notice: Bei A_INF, S_INF the following applies:
The value is updated with the current controller sampling time.
The following applies for SERVO:
The value is updated with a sampling time of 1 ms.
Note: Absolute current value = sqrt(Iq^2 + Id^2)
The absolute current actual value is available smoothed (r0027) and unsmoothed (r0068).
Description: Displays the DC current in the DC link.
Dependency: Refer to: r0027
Note: The DC current in the DC link is available smoothed (r0027) and unsmoothed (r0068).
Description: Displays actual absolute current.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0027
Notice: The value is updated with the current controller sampling time.
Note: Absolute current value = sqrt(Iq^2 + Id^2)
The absolute value of the current actual value is available smoothed (r0027 with 300 ms, r0068[1] with p0045) and
unsmoothed (r0068[0]).
r0068 CO: Absolute current actual value / I_act abs val
A_INF, SERVO,
S_INF
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 5730, 8014,
8850, 8950
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0068 CO: DC current in the DC link / Idc DC link
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8014, 8750
P-Group: Displays, signals Units group: 6_4 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r0068[0...1] CO: Absolute current actual value / I_act abs val
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6714, 6799,
8014
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]