EasyManua.ls Logo

Siemens SINAMICS S Series - p0740 BI: CX signal source for terminal DI;DO 10; CX S_src DI;DO 10; p0741 BI: CU, signal source for terminal DI;DO 11; CU S_src DI;DO 11; p0741 BI: CX signal source for terminal DI;DO 11; CX S_src DI;DO 11; p0742 BI: CU, signal source for terminal DI;DO 12; CU S_src DI;DO 12

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-230
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for terminal DI/DO 10 (X122.10).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Prerequisite: The DI/DO must be set as an output (p0728.10 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 11 (X122.11).
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
Note: Prerequisite: The DI/DO must be set as an output (p0728.11 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 11 (X122.11).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Prerequisite: The DI/DO must be set as an output (p0728.11 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the signal source for terminal DI/DO 12 (X132.7).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Prerequisite: The DI/DO must be set as an output (p0728.12 = 1).
DI/DO: Bidirectional Digital Input/Output
p0740 BI: CX signal source for terminal DI/DO 10 / CX S_src DI/DO 10
CU_CX32 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2231
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0741 BI: CU, signal source for terminal DI/DO 11 / CU S_src DI/DO 11
CU_S Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 1510, 2031,
2131
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0741 BI: CX signal source for terminal DI/DO 11 / CX S_src DI/DO 11
CU_CX32 Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2231
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0742 BI: CU, signal source for terminal DI/DO 12 / CU S_src DI/DO 12
CU_S Can be changed: U, T Calculated: - Access level: 1
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 1510, 2132
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0