List of parameters
Parameters
1-435
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for the scaling of the lower force limit or the regenerative force limit in p1523.
Dependency: p1400 bit 4 = 0: Upper / lower
p1400 bit 4 = 1: Motoring / generating
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values. that are obtained as a result of the signal source and the scaling can cause the motor to accelerate
in an uncontrollable fashion.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the scaling of the lower torque limit in p1523.
Danger: For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Positive values. that are obtained as a result of the signal source and the scaling can cause the motor to accelerate
in an uncontrollable fashion.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the power limit when motoring.
Dependency: Refer to: p0500, p1531
Note: For VECTOR the following applies (p0107):
The power limit is limited to 300% rated motor power.
p1529[0...n] CI: Force limit lower/regenerative scaling / F_max low/gen scal
SERVO (Lin) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 1610, 3617,
5620, 5630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1525[0]
p1529[0...n] CI: Torque limit lower scaling / M_max lower scal
VECTOR (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dynamic index: CDS, p0170 Func. diagram: 6630
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- - 1525[0]
p1530[0...n] Power limit motoring / P_max mot
SERVO, VECTOR
(n/M)
Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5640, 6640
P-Group: Closed-loop control Units group: 14_5 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.00 [kW] 100000.00 [kW] 0.00 [kW]