List of parameters
Parameters
1-699
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description: Sets the delay time for the zero current signal for the zero current monitoring.
Dependency: Refer to: p3207, p3208
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
Description: Sets the configuration word of the infeed.
Dependency: Refer to: p0210
Note: Re bit 00:
In the smart mode, the DC link voltage is not controlled - however, infeed can still regenerate. The magnitude of the
DC link voltage depends on the actual line supply voltage and the DC link load.
For drive units belonging to the 400 V voltage class, for a drive unit supply voltage (p0210) greater than 415 V, the
infeed is always operated in the smart mode. This means that the 660 V limit can be maintained for the steady-state
DC link voltage (p0280) up to a line supply voltage of 480 V.
Re bit 01:
If the flat top mode is deactivated, switching losses are higher. This means that the full power is no longer continu-
ously available.
For p3400.0 = 1, this bit is not effective.
Re bit 03:
If the Vdc controller is switched-out, overvoltage or undervoltage conditions occur in the DC link if no other voltage-
regulating component is located in the DC link.
For p3400.0 = 1, this bit is not effective.
Re bit 05:
VSM: Voltage Sensing Module
If a VSM is detected when commissioning the system, this bit is automatically set.
When the bit is set, the line supply voltage input of the VSM must be connected (connected at the line side of the
commutating reactor).
p3209[0...n] Zero current signal delay time / I_0_sig t_del
VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.00 [s] 10.00 [s] 0.02 [s]
p3400 Infeed configuration word / INF config_word
A_INF, S_INF Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 8940
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Smart Mode On Off -
01 Flat-top mode On Off -
03 Vdc controller On Off -
05 Line supply voltage sensing with VSM On Off -