List of parameters
Parameters
1-375
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
If p1335 is changed while commissioning (p0009, p0010 > 0), then it is possible that the old value will no longer be
able to be set. The reason for this is that the dynamic limits of p1335 have been changed by a parameter that was
set when the drive was commissioned (e.g. p0300).
Description: Sets the limit value for slip compensation in [%] referred to r0330 (motor rated slip).
Description: Displays the actual compensated slip [%] referred to r0330 (rated motor slip).
Dependency: p1335 > 0 %: Slip compensation active.
Refer to: p1335
Description: Sets the controller gain for resonance damping for V/f control.
Dependency: Refer to: p1300, p1339, p1349
Note: The resonance damping function dampens active current oscillations that frequency occur under no-load condi-
tions.
The resonance damping is active in a range of approximately 5 ... 90 % of the rated motor frequency (p0310), but
up to a maximum of 45 Hz.
For the open-loop control modes p1300 = 5 and 6 (textile sectors), the resonance damping is internally disabled in
order that the output frequency can be precisely set.
Description: Sets the filter time constant of the controller for resonance damping with V/f control.
Dependency: Refer to: p1300, p1338, p1349
p1336[0...n] Slip compensation limit value / Slip comp lim val
VECTOR Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6310
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
0.00 [%] 600.00 [%] 250.00 [%]
r1337 Actual slip compensation / Slip comp act val
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 6310
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1338[0...n] V/f mode resonance damping gain / Uf Res_damp gain
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 1690, 6310
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 100.00 0.00
p1339[0...n] V/f mode resonance damping filter time constant / Uf Res_damp T
VECTOR Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6310
P-Group: V/f open-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1.00 [ms] 1000.00 [ms] 20.00 [ms]