Faults and Alarms
List of faults and alarms
3-1510
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A02150 OA: Application cannot be loaded
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The system was not able to load an OA application.
Alarm value (r2124, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
Note:
OA: Open Architecture
See also: r4950 (OA application count), r4955 (OA application identifier), p4956 (OA application activation), r4957
(OA application version)
F02151 (A) OA: Internal software error
Drive object: All objects
Reaction: A_INFEED: OFF2 (NONE, OFF1)
SERVO: OFF2 (NONE, OFF1, OFF3)
VECTOR: OFF2 (NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An internal software error has occurred within an OA application.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (power off/on) for all components.
- upgrade the firmware release.
- contact the Hotline.
- replace the Control Unit.
Note:
OA: Open Architecture
See also: r4950 (OA application count), r4955 (OA application identifier), p4956 (OA application activation), r4957
(OA application version)
Reaction upon A: NONE
Acknowl. upon A: NONE
F02152 (A) OA: Insufficient memory
Drive object: All objects
Reaction: OFF1
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Too many functions have been configured on this Control Unit (e.g. too many drives, function modules, data sets,
OA applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - change the configuration on this Control Unit (e.g. fewer drive, function modules, data sets, OA applications, blocks,
etc).
- use an additional Control Unit.
Note:
OA: Open Architecture
Reaction upon A: NONE
Acknowl. upon A: NONE