A07585 Encoder 2: Position setting value activated
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The position actual value is set to the value received via CI: p2515while BI: p2514 = 1 signal. A possible system
deviation cannot be corrected.
Remedy: None necessary.
The alarm automatically disappears with BI: p2514 = 0 signal.
A07586 Encoder 3: Position setting value activated
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The position actual value is set to the value received via CI: p2515while BI: p2514 = 1 signal. A possible system
deviation cannot be corrected.
Remedy: None necessary.
The alarm automatically disappears with BI: p2514 = 0 signal.
A07587 Encoder 1: Position actual value preprocessing does not have a valid encoder
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy: Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0189
(Encoder 3 encoder data set number), p0400 (Enc type selection), p2502 (LR encoder assignment)
A07588 Encoder 2: Position actual value preprocessing does not have a valid encoder
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy: Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0189
(Encoder 3 encoder data set number), p0400 (Enc type selection), p2502 (LR encoder assignment)
A07589 Encoder 3: Position actual value preprocessing does not have a valid encoder
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The following problem has occurred during the position actual value preprocessing.
- an encoder data set has been assigned, however, the encoder data set does not contain any encoder data (p0400
= 0) or invalid data (e.g. p0408 = 0).
Remedy: Check the drive data sets, encoder data sets.
See also: p0187 (Encoder 1 encoder data set number), p0188 (Encoder 2 encoder data set number), p0189
(Encoder 3 encoder data set number), p0400 (Enc type selection), p2502 (LR encoder assignment)