Parameters
List of parameters
1-120
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Enter the inductance of a filter connected at the power unit output.
Dependency: The parameter is automatically pre-assigned when selecting a filter via p0230.
Refer to: p0230
Description: Enters the capacitance of a sinusoidal filter connected at the power unit output.
Dependency: The parameter is automatically pre-assigned when selecting a filter via (p0230).
Refer to: p0230
Note: The parameter value includes the sum of all of the capacitances of a phase connected in series (phase - ground).
Description: Number of reactors connected at the power unit output.
Dependency: Refer to: p0230
Caution: If the number of motor reactors connected in series does not correspond to the parameter value, then this can
result in an unfavorable control behavior.
Note: The parameter cannot be changed for chassis drive units and for p0230 = 1.
Description: Sets the cooling type for booksize compact power units.
This therefore defines whether for these power units, the internal air cooling is shut down and instead, the "Cold-
Plate" cooling type is used.
Values: 0: Air cooling internal
1: Cold-Plate
Note: For booksize compact power units, there is a 4 at the 5th position in the Order No.
The parameter is irrelevant for all other power unit types.
p0233 Power unit motor reactor / PU mot reactor
VECTOR Can be changed: C2(2), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [mH] 1000.000 [mH] 0.000 [mH]
p0234 Power unit sinusoidal filter capacitance / PU sine filter C
VECTOR Can be changed: C2(2), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [µF] 1000.000 [µF] 0.000 [µF]
p0235 Number of reactors connected in series / Qty L in series
VECTOR Can be changed: C2(1, 2) Calculated: - Access level: 1
Data type: Unsigned8 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 3 1
p0249 Power unit cooling type / PU cool type
SERVO, S_INF,
VECTOR
Can be changed: C2(1, 2) Calculated: - Access level: 4
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 0