1-724
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Note: When the 690 V input is used (X522) without voltage scaler,, 0 % should be entered.
When the 100 V input (X521) is used with voltage scaler to measure medium voltages, the dividing (scaling) factor
multiplied by 100% should be entered.
Example:
1000 V line supply voltage, voltage scaling, 10:1
--> voltage at the VSM input is 100 V
--> p3660 = 10 * 100 % = 1000 %
Description: Sets the voltage scaler for the Voltage Sensing Module (VSM).
Note: When the 690 V input is used (X522) without voltage scaler,, 0 % should be entered.
When the 100 V input (X521) is used with voltage scaler to measure medium voltages, the dividing (scaling) factor
multiplied by 100% should be entered.
Example:
1000 V line supply voltage, voltage scaling, 10:1
--> voltage at the VSM input is 100 V
--> p3660 = 10 * 100 % = 1000 %
Description: Displays the voltage between L1 and L2.
Dependency: Refer to: r0025, r0072, p3660
Note: X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
The absolute voltage value (3-ph. AC) resulting from the phase voltages is displayed unsmoothed in r0072[1] and
smoothed in r0025[1].
Description: Displays the voltage between L1 and L2.
Dependency: Refer to: p3660
Note: X521.1 or X522.1: Connection of L1
X521.2 or X522.2: Connection of L2
X521.3 or X522.3: Connection of L3
p3660[0...n] VSM input line supply voltage, voltage scaler / VSM inp V_scaler
VECTOR Can be changed: T Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [%] 100000.00 [%] 0.00 [%]
r3661 CO: VSM input line supply voltage u1 - u2 / VSM inp u1-u2
A_INF, S_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950,
9880
P-Group: Closed-loop control Units group: 5_3 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]
r3661[0...n] CO: VSM input line supply voltage u1 - u2 / VSM inp u1-u2
VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: p0150 Func. diagram: -
P-Group: Closed-loop control Units group: 5_3 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]