Function Diagrams
Terminal Board 30 (TB30)
2-1376
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-247 9102 – Digital outputs, electrically isolated (DO 0 ... DO 3)
- 9102 -
Function diagram
87654321
fp_9102_51_eng.vsd
DO: TB30
SINAMICS
30.07.07 V02.05.00
Terminal Board 30 (TB30) - Digital outputs, electrically isolated (DO 0 ... DO 3)
DO 3 X481.8
DO 0
DO 1
DO 2
X481.7
p4048.0
p4048.1
p4048.2
p4048.3
X481.5
X481.6
24 V
5 V
Mext
<1>
<1>
X424.M
X424.+
X424.M
24 V DC to the next device
X424.+
+24 Vext
+24 Vext
Mext
Mext
+
p4099[0] (4000.00 µs)
1
0
1
1
0
1
1
0
1
1
0
1
<1> Mext electrically isolated to the internal CU reference potential M.
(0)
TB30 S_src DO 3
p4033
(0)
TB30 S_src DO 2
p4032
(0)
TB30 S_src DO 1
p4031
(0)
TB30 S_src DO 0
p4030
DO 0 (X481.5)
r4047.0
DO 1 (X481.6)
r4047.1
DO 2 (X481.7)
r4047.2
DO 3 (X481.8)
r4047.3