Parameters
List of parameters
1-270
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays or sets the PROFIBUS address for PROFIBUS interface (X126) on the Control Unit.
The address can be set as follows:
1) Using the DIP switch power-up the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> only if all of the DIP switches - from S1 to S7 - are either set to ON or OFF.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
Description: Sets the send and receive telegram.
Values: 390: SIEMENS telegram 390, PZD-2/2
391: SIEMENS telegram 391, PZD-3/7
392: SIEMENS telegram 392, PZD-3/15
999: Free telegram configuration with BICO
Description: Sets the send and receive telegram.
Values: 370: SIEMENS telegram 370, PZD-1/1
999: Free telegram configuration with BICO
Dependency: Refer to: F01505, F01506
Note: If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are inhib-
ited.
The inhibited interconnections can only be changed again after setting value 999.
p0918 PROFIBUS address / PB address
CU_CX32, CU_S Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2410
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1 126 126
p0922 PROFIdrive telegram selection / PD Telegr_sel
CU_CX32, CU_S Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2423, 2448, 2449, 2458, 2459,
2481, 2483
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
390 999 999
p0922 PROFIdrive telegram selection / PD Telegr_sel
A_INF, B_INF,
S_INF
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dynamic index: - Func. diagram: 1520, 2420,
2423, 2447, 2457, 2481, 2483
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
370 999 999