EasyManua.ls Logo

Siemens SINAMICS S Series - Figure 2-212 8065 - Alarm buffer

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and alarms
Function Diagrams
2-1335
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-212 8065 – Alarm buffer
- 8065 -
Function diagram
87654321
fp_8065_51_eng.vsd
DO: All objects
SINAMICS
10.11.06 V02.05.00
Faults and alarms - Alarm buffer
Alarm value
Alarm time
"come"
Alarm time
"removed"
Alarm code
RESET
Alarm comes
Alarms
counter
p2111
p2111 = 0:
Alarm buffer is deleted
1
Delete alarm buffer
r2122 = 0
r2123 = 0
r2124 = 0
r2125 = 0
r2134 = 0
r2145 = 0
r2146 = 0
Alarm goes
Alarm comes
1
Alarm buffer change
r2121
Counter
16 bit
III
RESET
III
RESET
Fault buffer change [8060.8]
Sum, buffer changed
r2120
III
RESET
1
Fault/alarm buffer changes from
other drive objects
POWER ON
16 bit counter,
free running
16 bit counter,
free running
Alarm number
r2110
Operating time
Alarm times
Alarm buffer
change
POWER ON
r2132
Actual alarm code
0 = "No alarm present"
External alarm 1
r2138.10
External alarm 2
r2138.11
External alarm 3
r2138.12
[2548.2]
Background
Refer to [1020.7]
[2546.7]
p2112
[2546.7]
p2116
[2546.7]
p2117
r2122[0]
r2122[1]
r2122[7]
r2124[0] [I32]
r2134[0] [Float]
r2124[1] [I32]
r2134[1] [Float]
r2124[7] [I32]
r2134[7] [Float]
r2123[0] [ms]
r2145[0] [d]
r2123[1] [ms]
r2145[1] [d]
r2123[7] [ms]
r2145[7] [d]
r2125[0] [ms]
r2146[0] [d]
r2125[1] [ms]
r2146[1] [d]
r2125[7] [ms]
r2146[7] [d]
[8060.1]
Alarm 1
(oldest)
Alarm 2
Alarm 8
(most recent)
POWER ON
Alarm present
r2139.7
r2122[8]
r2122[9]
r2122[63]
r2124[8] [I32]
r2134[8] [Float]
r2124[9] [I32]
r2134[9] [Float]
r2124[63] [I32]
r2134[63] [Float]
r2123[8] [ms]
r2145[8] [d]
r2123[9] [ms]
r2145[9] [d]
r2123[63] [ms]
r2145[63] [d]
r2125[8] [ms]
r2146[8] [d]
r2125[9] [ms]
r2146[9] [d]
r2125[63] [ms]
r2146[63] [d]
Alarm 1
(most recent)
Alarm 2
Alarm 56
(oldest)
Alarm history
<1> The buffer parameters are updated cyclically in the background (see status signal in r2139).
<1>
Control Unit
Warning Present
r3114.9

Table of Contents

Related product manuals