List of parameters
Parameters
1-351
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the monitoring time of the contactor feedback signal for the external armature short-circuit configuration.
If the contactor feedback signal (p1235) is parameterized, then the appropriate feedback signal (r1239.1) is
expected within this monitoring time after either opening or closing the contactor.
Dependency: Refer to: p1230, p1231, p1235, p1237, r1239
Refer to: A07904, F07905
Description: Sets the delay time when opening the contactor of the external armature short-circuit.
If no contactor feedback signal has been selected (p1235), then the system waits for this time before the pulses are
switched-in.
Dependency: Refer to: p1230, p1231, p1235, p1236, r1239
Notice: This delay time must be at least long enough so that the contactor contacts reliably open before the pulses are
switched-in. The delay time must be greater than the contactor response time. The Motor Module can be damaged
if the delay time is too short.
Description: Displays the state for the external armature short-circuit.
Values: 0: Powered-down
1: Ready
2: active
3: Active - feedback signal "Closed" OK
4: Active - feedback signal "Closed" missing
5: Prompt to remove the armature short-circuit
6: Active - feedback signal "Open" missing
Dependency: Refer to: p1230, p1231, p1235, p1236, p1237, r1239
Refer to: A07904, F07905
Note: Activation criteria (one of the following criteria is fulfilled):
- the signal at BI: p1230 (armature short-circuit activation) is 0.
- the drive is not in the state "S4: Operation" or in S5x (refer to function chart 2610).
- the internal pulse enable is missing (r0046.19 = 0).
Re state "switched-out" (r1238 = 0):
- the external armature short-circuit can be selected with p1231 = 1.
p1236[0...n] Ext. armature short-cct., contactor feedback signal monit. time / ASC ext t_monit
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 200 [ms]
p1237[0...n] External armature short-circuit, waiting time when opening / ASC ext t_wait
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 1
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 200 [ms]
r1238 CO: Armature short-circuit, external state / EASC state
SERVO, VECTOR Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 2610
P-Group: Functions Units group: - Unit selection: -
Not for motor type: ASM Expert list: 1
Min Max Factory setting
0 6 -