Signals and monitoring functions
Function Diagrams
2-1329
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-207 8013 – Load monitoring (r0108.17 = 1)
- 8013 -
Function diagram
87654321
fp_8013_01_eng.vsd
DO: SERVO, VECTOR
SINAMICS S
30.07.07 V02.05.00
Signals and monitoring functions - Load monitoring (r0108.17 = 1)
r0080
M_act
r2169
n_act smooth signal
[8010.2]
[5730.1]
[6714.8]
A07920 ... A07922
r2198.11
[2536.3]
n_threshold 1
0.00...210 000.00 RPM
p2182[D](150.00)
n_threshold 2
0.00...210 000.00 RPM
p2183[D](900.00)
n_threshold 3
0.00...210 000.00 RPM
p2184[D](1500.00)
n [RPM]
M [Nm]
F07923 ... F07925
r2198.12
[2536.3]
0T
0.00...65.00 s
p2192[D] (10.00)
Load monitoring response
p2181[D](0)
Evaluation
A07920 "Torque too low"
A07921 "Torque too high"
A07922 "Torque outside tolerance"
A07923 "Torque too low"
A07924 "Torque too high"
A07925 "Torque outside tolerance"
A07926 "Envelop characteristic, parameter not value"
Tolerance
bandwidth
<1>
<1> The response to these faults can be defined.
(0)
(1)
Load monitoring disabled
(2)
(3)
(4)
(5)
(6)
<1>
<1>
p0115[3] (4000.00 µs)
0
1
p2149.1
0
1
p2149.1
M_thresh 3 upper
0.00...20 000 000.00 Nm
p2189[D] (10 000 000.00)
M_thresh 3 lower
0.00...20 000 000.00 Nm
p2190[D] (0.00)
M_thresh 2 upper
0.00...20 000 000.00 Nm
p2187[D] (10 000 000.00)
M_thresh 2 lower
0.00...20 000 000.00 Nm
p2188[D] (0.00)
M_thresh 1 upper
0.00...20 000 000.00 Nm
p2185[D] (10 000 000.00)
M_thresh 1 lower
0.00...20 000 000.00 Nm
p2186[D] (0.00)