List of parameters
Parameters
1-213
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the alarm threshold 1 for monitoring the motor temperature.
Note: The alarm threshold is not, as for p0604, coupled to the timer p0606.
Description: Sets the thermal adaptation of the stator/primary section resistance and rotor/secondary section resistance accord-
ing to r0395 and r0396.
Values: 0: No thermal adaptation of stator and rotor resistances
1: Resistances adapted to the temperatures of the thermal model
2: Resistances adapted to the measured stator winding temperature
Note: For p0620 = 1, the following applies:
The stator resistance is adapted using the temperature in r0035 and the rotor resistance together with the model
temperature in r0633.
For p0620 = 2, the following applies:
The stator resistance is adapted using the temperature in r0035. The rotor temperature to adapt the rotor resistance
is calculated as follows from the stator temperature (r0035).
theta_R = (r0628 + r0625) / (r0627 + r0625) * r0035
Description: Sets the thermal adaptation of the stator/primary section resistance and rotor/secondary section resistance accord-
ing to r0395 and r0396.
Values: 0: No thermal adaptation of stator and rotor resistances
1: Resistances adapted to the temperatures of the thermal model
2: Resistances adapted to the measured stator winding temperature
Note: For p0620 = 1, the following applies:
The stator resistance is adapted using the temperature in r0035 and the rotor resistance together with the model
temperature in r0633.
For p0620 = 2, the following applies:
The stator resistance is adapted using the temperature in r0035. The rotor temperature to adapt the rotor resistance
is calculated as follows from the stator temperature (r0035).
theta_R = (r0628 + r0625) / (r0627 + r0625) * r0035
p0616[0...n] Motor overtemperature alarm threshold 1 / Mot temp alarm 1
VECTOR Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 130.0 [°C]
p0620[0...n] Thermal adaptation, stator and rotor resistance / Mot therm_adapt R
SERVO Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 2
p0620[0...n] Thermal adaptation, stator and rotor resistance / Mot therm_adapt R
VECTOR Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 2
Data type: Integer16 Dynamic index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 2 1