Parameters
List of parameters
1-468
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the scaling of the dynamic current controller pre-control for the torque/force-generating current component Isq.
Description: Sets the scaling of the EMF pre-control for the Isq current controller.
Description: Threshold for the setpoint - actual value tracking of the EMF pre-control of the Isq current controller.
Description: Sets the proportional gain of the current controller for the lower adaptation current range. This value is automatically
preset using p3900 or p0340 when commissioning has been completed.
Dependency: p0391, p0392 and p0393 are only available for SERVO.
Refer to: p0391, p0392, p0393
Note: For p0393 = 100 %, the current controller adaptation is disabled and p1715 is effective over the entire range.
Description: Sets the proportional gain of the current controller for the lower adaptation current range. This value is automatically
preset using p3900 or p0340 when commissioning has been completed.
p1703[0...n] Isq current controller pre-control scaling / Isq_ctr_prectrScal
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 70.0 [%]
p1704[0...n] EMF scaling of the Isq current controller pre-control / EMF scal Isq_ctrl
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.0 [%] 200.0 [%] 100.0 [%]
p1705[0...n] Flux setpoint/actual value tracking threshold / Flux track thresh
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 100.0 [%]
p1715[0...n] Current controller P gain / I_ctrl Kp
SERVO Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5714, 6714
P-Group: Closed-loop control Units group: 18_1 Unit selection: p0505
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.000 [V/A] 100000.000 [V/A] 0.000 [V/A]
p1715[0...n] Current controller P gain / I_ctrl Kp
VECTOR (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 3
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: 5714, 6714
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
0.000 100000.000 0.000