Faults and Alarms
List of faults and alarms
3-1660
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F31886 (N, A) CU DRIVE-CLiQ: Error when sending DRIVE-CLiQ data
Drive object: All objects
Reaction: A_INFEED: NONE (OFF1, OFF2)
SERVO: ENCODER (IASC / DCBRAKE, NONE)
VECTOR: ENCODER (IASC / DCBRAKE, NONE)
Acknowledge: IMMEDIATELY
Cause: DRIVE-CLiQ communications error between the Control Unit and the encoder involved (encoder 1). Data were not
able to be sent.
Fault value (r0949, interpret hexadecimal):
41: Telegram type does not match send list.
Remedy: - carry out a POWER ON.
- check whether the firmware version of the encoder (r0148) matches the firmware version of Control Unit (r0018).
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F31887 (N, A) CU DRIVE-CLiQ: Component fault
Drive object: All objects
Reaction: A_INFEED: NONE (OFF1, OFF2)
SERVO: ENCODER (IASC / DCBRAKE, NONE)
VECTOR: ENCODER (IASC / DCBRAKE, NONE)
Acknowledge: IMMEDIATELY
Cause: Fault detected on the DRIVE-CLiQ component involved (Sensor Module for encoder 1). Faulty hardware cannot be
excluded.
Fault value (r0949, interpret hexadecimal):
20: Error in the telegram header.
23: Receive error: The telegram buffer memory contains an error.
42: Send error: The telegram buffer memory contains an error.
43: Send error: The telegram buffer memory contains an error.
60: Response received too late during runtime measurement.
61: Time taken to exchange characteristic data too long.
Remedy: - check the DRIVE-CLiQ wiring (interrupted cable, contacts, ...).
- check the electrical cabinet design and cable routing for EMC compliance
- if required, use another DRIVE-CLiQ socket (p9904).
- replace the component involved.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F31895 (N, A) CU DRIVE-CLiQ: Cyclic data transfer error
Drive object: All objects
Reaction: A_INFEED: NONE (OFF1, OFF2)
SERVO: ENCODER (IASC / DCBRAKE, NONE)
VECTOR: ENCODER (IASC / DCBRAKE, NONE)
Acknowledge: IMMEDIATELY
Cause: DRIVE-CLiQ communications error between the Control Unit and the encoder involved (encoder 1).
Fault value (r0949, interpret hexadecimal):
0B: Synchronization error during alternating cyclic data transfer.
Remedy: Carry out a POWER ON.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE