List of parameters
Parameters
1-249
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for control word 1 bit 0 (ON/OFF1).
Dependency: Refer to: p1055, p1056
Notice: For BI: p0840 = 0 signal, the motor can be moved, jogging using BI: p1055 or BI: p1056.
The command "ON/OFF1" can be issued using BI: p0840 or using BI: p1055/p1056.
Only the signal source that originally powered-up can also power-down again.
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 0 = 0: OFF1 (pulse cancelation and power-on inhibit)
Bit 0 = 0/1: ON (pulses can be enabled)
Description: Sets the signal source for the 1st OC/OFF2.
The AND logic operation of the 1st OC/OFF2 and 2nd OC/OFF2 results in control word 1, bit 1 (OC/OFF2).
Caution: When "master control from PC" is activated, this binector input is ineffective.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: For drives, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancelation and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
For infeed units, the following applies:
Bit 1 = 0: OFF2 (immediate pulse cancelation for active infeed modules and Smart Line Modules, pre-charging con-
tactor/line contactor open and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
OC: Operating condition
Description: Sets the signal source for control word 1, bit 1 (OC/OFF2).
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note: Bit 1 = 0: OFF2 (immediate pulse cancelation and power-on inhibit)
Bit 1 = 1: No OFF2 (enable is possible)
OC: Operating condition
p0840 BI: ON/OFF1 / ON/OFF1
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p0844[0...n] BI: 1. OFF2 / 1. OFF2
A_INF, B_INF,
SERVO, S_INF,
VECTOR
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: 2501, 8720,
8820, 8920
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p0844 BI: OFF2 / OFF2
TM41 Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1