List of parameters
Parameters
1-59
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays missing enable signals that are preventing the closed-loop drive control from being commissioned.
Dependency: Refer to: r0002
Note: The value r0046 = 0 indicates that all enable signals for this drive are present.
Bit 00 = 1 (enable signal missing), if:
- the signal source in p0840 is a 0 signal.
- there is a power-on inhibit.
Bit 01 = 1 (enable signal missing), if:
- the signal source in p0844 or p0845 is a 0 signal.
Bit 02 = 1 (enable signal missing), if:
- the signal source in p0848 or p0849 is a 0 signal.
Bit 03 = 1 (enable signal missing), if:
- the signal source in p0852 is a 0 signal.
Bit 04 =1 (armature short-circuit active), if:
- the signal source in p1230 has a 1 signal
Bit 05, Bit 06: Being prepared
Bit 08 = 1 (enable signal missing), if:
- the pulse enable via terminal EP is missing (booksize: X21, chassis: X41).
Bit 09 = 1 (enable signal missing), if:
- the signal source in p0864 is a 0 signal.
r0046.0...31 CO/BO: Missing enable sig / Missing enable sig
SERVO (Lin) Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dynamic index: - Func. diagram: 2634
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OFF1 enable missing Yes No -
01 OFF2 enable missing Yes No -
02 OFF3 enable missing Yes No -
03 Enable operation missing Yes No -
04 Armature short-circuit / DC current brake,
enable missing
Yes No 7014,
7016
05 STOP2 enable missing Yes No -
06 STOP1 enable missing Yes No -
08 EP terminals enable missing Yes No -
09 Infeed enable missing Yes No -
10 Ramp-function generator enable missing Yes No -
11 Ramp-function generator start missing Yes No -
12 Setpoint enable missing Yes No -
16 OFF1 enable internal missing Yes No -
17 OFF2 enable internal missing Yes No -
18 OFF3 enable internal missing Yes No -
19 Pulse enable internal missing Yes No -
20 Armature short-circuit/DC current brake
internal enable missing
Yes No 7014,
7016
21 STOP2 enable internal missing Yes No -
22 STOP1 enable internal missing Yes No -
25 Function bypass active Yes No -
26 Drive inactive or not operational Yes No -
27 Demagnetization not completed Yes No -
28 Brake open missing Yes No -
29 Cooling system ready signal missing Yes No -
30 Velocity controller inhibited Yes No -
31 Jog setpoint active Yes No -