Function Diagrams
Safety Integrated
2-1212
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-100 2810 – Basic functions, STO (Safe Torque Off)/SS1 (Safe Stop 1)
- 2810 -
Function diagram
87654321
fp_2810_01_eng.vsd
DO: SERVO, VECTOR
SINAMICS S
12.07.07 V02.05.01
Safety Integrated - Basic Functions, STO (Safe Torque Off)/SS1 (Safe Stop 1)
Motor Module
1 = STO active on Control Unit
r9772.1
[2804.2]
r9880 (Motor Modules)
<6>
Motor Module
r0722.3
r0722.4
<1>
F01611 (CU)
F30611 (MM)
1
1 = STOP A [2802.8]
&
<4>
1
1 = STOP A [2802.8]
&
EP M
+24 V
X21/22 EP +
M
~
U
V
W
+ Vdc
-Vdc
1
&
+5 V
+5 V
M
Shutdown path
from MM
0 = STO_MM
+24 V
<3>
[2802.1][2814.2] DIAG_L
[2802.1][2814.2] DIAG_U
<5>
<5>
1
[2802.2]
[2802.2]
[2802.2]
T0
T0
[2802.2]
[2804.1]
[2802.2]
[2804.1]
SS1: Safe Stop 1
&
p9620[3]
p9620[7]
r0722.7
r0722.0
0 = Safe Torque Off CU
p9620[0]
p9620[4]
p0120
&
<7>
Upper IGBT
bridge halve
Gating unit
Lower IGBT
bridge halve
<1> One terminal can be used for several drives to form a group.
<2> Switch-on delay according to [1024], starts when the "request pulse cancelation CU" is withdrawn.
<3> Value range: p9620 = 0 or r0722.0...7 (for CU310 and CX32 only r0722.0...3).
<4> Redundant functions in the Control Unit (CU) and Motor Modules (MM).
<5> Transistors inhibited for a "0" signal.
<6> Only for Booksize.
<7> Only for VECTOR. The number of active AND inputs corresponds to the number of Motor Modules
connected in parallel (p0120).
STO: Safe Torque Off / SH: Safe standstill
Gating unit
0 = Request pulse cancelation MM
1 = STO on MM active
r9872.1
[2804.5]
1 = "STO active" for
sequence control
F-DI chg tol CU p9650
F-DI chg tol MM p9850
0...2000 ms (500 ms)
Safe pulse cancelation
Monitoring for simultaneous occurrence
to SBC
[2814.2]
Shutdown path
from CU
0 = STO_CU
to SBC
[2814.2]
[2804.5]
1 = STO selected on MM
r9872.0
SI Stop 1 t_del MM
0.00...300000.00 [s]
p9852 (0.00)
1 = Safety commissioning mode [2800.3]
Redundant functions
r9772.2 SS1 active on Control Unit
r9872.2 SS1 active on Motor Module
0 = Request Pulse
cancelation CU
T0
A01699
"Shutdown
paths must
be tested"
Timer forced
checking procedure
0...9000 h
p9659(8)
DRIVE-CLiQ
r9780 Control Unit
Timer for forced
checking procedure
<2>
1 = Shutdown
paths must
be tested
r9773.31
[2804.7]
T
Control Unit
[2804.2]
1 = STO selected on CU
r9772.0
Additional for
CU320,
SIMOTION,
Dxxx and
NCU7xx
CU terminals that can be used for STO.
1 = Safety
commissioning mode
[2800.3]
SI Stop 1 t_del CU
0.00...300.00 [s]
p9652 (0.00)
EP: Enable Pulses
&
1 = STO release [2825.8]
1
1 = Enable SOS/SLS p9301.0
1 = Enable STO (SH) via terminals (MM) p9801.0
1
1
&
1 = STO release
[2825.8]
&
1
1 = Enable STO (SH) via
terminals (CU) p9601.0
1 = Enable SOS/SLS
(SBH/SG) p9501.0
=1
T0