Parameters
List of parameters
1-80
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Setting to pre-assign/check the sampling times for the internal controller clock cycles for clock synchronous PROFI-
BUS operation.
p0092 = 1:
The controller clock cycles are set so that clock synchronous PROFIBUS operation is possible. If it is not possible
to change the controller clock cycles of the clock synchronous PROFIBUS operation, then an appropriate mes-
sage/signal is output.
The pre-setting of the controller clock cycles can result in a de-rating of the Motor Module (e.g. p0115[0] = 400 µs -
-> 375 µs).
p0092 = 0:
The controller clock cycles are set without any restrictions by the clock synchronous PROFIBUS operation (as for
up to version V2.3).
Dependency: Refer to: r0110, p0115
Refer to: A01223, A01224
Description: Displays the normalized electrical pole position angle.
Dependency: Refer to: r0094, p0431, r1778
Notice: For p1821 = 1 (rotating field reversal), the following applies:
In order to adjust the encoder using the EMF method, the value, determined using the oscilloscope, must be
inverted and then entered in p0431.
Note: For operation with encoder and pulse cancelation, the following applies:
- the value is generated from r0094 + 180 °.
- this angle can be used to adjust the encoders of synchronous motors.
For pulse enable, the following applies:
- the value indicates the transformation angle used by the control + 180 °.
- this value is, contrary to r0094, also applicable (provides information) for sensorless operation and after a pole
position identification routine.
Description: Displays the transformation angle.
Note: The transformation angle corresponds to the line supply angle.
p0092 Clock synchronous operation pre-assignment/check / Clock sync op
CU_CX32 Can be changed: C1(1) Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 1 1
r0093 CO: Pole position angle electrically normalized / Pole pos el norm
SERVO Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
r0094 CO: Transformation angle / Transformat_angle
A_INF, S_INF Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 8850, 8950
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]