Siemens SINAMICS S Series - A01921 (F) PROFIBUS: Receive setpoints after To; A01930 IF1: PB;PN current controller clock cycle clock cycle synchronous not equal; A01931 IF1: PB;PN speed controller clock cycle clock cycle synchronous not equal; A01932 IF1: PB;PN clock cycle synchronization missing for DSC

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of faults and alarms
Faults and Alarms
3-1499
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Remedy: Set up the PROFIBUS connection and activate the PROFIBUS master in the cyclic mode.
Reaction upon F: NONE (OFF1)
Acknowl. upon F: IMMEDIATELY
A01921 (F) PROFIBUS: Receive setpoints after To
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: Output data of PROFIBUS master (setpoints) received at the incorrect instant in time within the PROFIBUS clock
cycle.
Remedy: - check bus configuration.
- check parameters for clock cycle synchronization (ensure To > Tdx).
Note:
Zo: Time of setpoint acceptance
Tdx: Data exchange time
Reaction upon F: NONE (OFF1)
Acknowl. upon F: IMMEDIATELY
A01930 IF1: PB/PN current controller clock cycle clock cycle synchronous not equal
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The current controller clock cycle of all drives must be set the same for the clock cycle synchronous operation.
Alarm value (r2124, interpret decimal):
Number of the drive object with the different current controller clock cycle.
Remedy: Set current controller clock cycles to identical values (p0115[0]).
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
See also: p0115 (Sampling time for supplementary functions)
A01931 IF1: PB/PN speed controller clock cycle clock cycle synchronous not equal
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The speed controller clock cycle of all drives must be set the same for the clock cycle synchronous operation.
Alarm value (r2124, interpret decimal):
Number of the drive object with the different speed controller clock cycle.
Remedy: Set the speed controller clock cycles the same (p0115[1]).
Note:
IF1: Interface 1
PB: PROFIBUS
PN: PROFINET
See also: p0115 (Sampling time for supplementary functions)
A01932 IF1: PB/PN clock cycle synchronization missing for DSC
Drive object: SERVO, TM41
Reaction: NONE
Acknowledge: NONE
Cause: There is not clock cycle synchronization and DSC is selected.
Note:
DSC: Dynamic Servo Control
Remedy: Set the clock cycle synchronization when configuring the bus.