List of parameters
Parameters
1-41
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Values: 0: Ready
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 15 (TM15).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
29: Download
30: Parameter reset
Dependency: Refer to: p0970
Note: Only the following values are possible: p0010 = 0, 30
Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the parameter filter for commissioning a Terminal Module 54F (TM54F).
Setting this parameter filters-out the parameters that can be written into in the various commissioning steps.
For the BOP, this setting also causes the read access operations to be filtered.
Values: 0: Ready
29: Download
30: Parameter reset
95: Safety Integrated commissioning
Dependency: Refer to: p0970
Note: Procedure for "Reset parameter": Set p0010 to 30 and p0970 to 1.
Description: Sets the password for the Basic Operator Panel (BOP).
Dependency: Refer to: p0012, p0013
p0010 TM15DI/DO commissioning the parameterizing filter / TM15D com par_filt
TM15DI_DO Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 30 0
p0010 TM54F commissioning parameter filter / TM54F com par_filt
TM54F_MA Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 95 0
p0011 BOP password entry (p0013) / BOP passw ent p13
CU_S Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 65535 0