List of faults and alarms
Faults and Alarms
3-1447
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F01105 (A) CU: Insufficient memory
Drive object: All objects
Reaction: OFF1
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Too many functions have been configured on this Control Unit e.g. too many drives, function modules, data sets, OA
applications, blocks, etc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - change the configuration on this Control Unit (e.g. fewer drive, function modules, data sets, OA applications, blocks,
etc).
- use an additional Control Unit.
Reaction upon A: NONE
Acknowl. upon A: NONE
F01107 CU: Save to CompactFlash card unsuccessful
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: A data save on the CompactFlash card was not able to be successfully carried out.
- CompactFlash card is defective.
- CompactFlash card does not have sufficient memory space.
Fault value (r0949, interpret decimal):
-1: The file on the RAM was not able to be opened.
-2: The file on the RAM was not able to be read.
-3: A new directory was not able to be set-up on the CompactFlash card.
-4: A new file was not able to be set-up on the CompactFlash card.
-5: A new file was not able to be written onto the CompactFlash card.
Remedy: - try to save again.
- use another CompactFlash card.
F01110 CU: More than one SINAMICS G on one Control Unit
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: More than one SINAMICS G power unit type is being operated from the Control Unit.
Fault value (r0949, interpret decimal):
Number of the second drive with a SINAMICS G power unit type.
Remedy: Only one SINAMICS G drive type is permitted.
F01111 CU: SINAMICS S and G together on one Control Unit
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: SINAMICS S and G drive units are being operated together on one Control Unit.
Fault value (r0949, interpret decimal):
Number of the first drive object with a different power unit type.
Remedy: Only power units of one particular drive type may be operated with one Control Unit.
F01112 CU: Power unit not permissible
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The connected power unit cannot be used together with this Control Unit.
Fault value (r0949, interpret decimal):
1: Power unit is not supported (e.g. PM240).
2: DC/AC power unit connected to CU310 not permissible.
Remedy: Replace the power unit that is not permissible by a component that is permissible.