Parameters
List of parameters
1-796
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Displays the currently referred input value of the analog inputs of terminal module 31 (TM31).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Note: AI: Analog Input
Description: Displays the currently referred input value of the analog inputs of terminal module 41 (TM41).
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI 0 (X523.1/X523.2)
Note: AI: Analog Input
Description: Displays the type of analog inputs.
Values: 4: Bipolar voltage input (-10 V ... +10 V)
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Description: Sets the type of analog inputs of terminal module 31 (TM31).
p4056[x] = 0, 4 correspond to a voltage input (r4052, p4057, p4059 are displayed in V).
p4056[x] = 2, 3, 5 correspond to a current input (r4052, p4057, p4059 are displayed in mA).
In addition, the associated switch S5 must be switched.
For a voltage input, S5.1 or S5.2 must be switched to setting V.
For a current input, S5.1 and S5.2 must be switched into setting I (load resistor = 250 Ohm is switched-in).
r4055[0...1] CO: TB31 analog inputs, actual value in percent / TM31 AI value in %
TM31 Can be changed: - Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 1840, 9566,
9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r4055[0...0] CO: TB41 analog inputs, actual value in percent / TM41 AI value in %
TM41 Can be changed: - Calculated: - Access level: 1
Data type: Floating Point Dynamic index: - Func. diagram: 9663
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r4056[0...1] TB30 analog inputs, type / TB30 AI type
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
4 4 -
p4056[0...1] TM31 analog inputs, type / TM31 AI type
TM31 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dynamic index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 5 4