List of parameters
Parameters
1-985
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Dependency: Refer to: p9331, p9380, p9563
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Values 10 to 14 are being prepared and are presently ineffective.
Note: A change only becomes effective after a POWER ON.
SLS: Safely-Limited Speed / SG: Safely reduced speed
Description: Setting to select and de-select the acceptance test mode.
Values: 0: [00 hex] De-select the acceptance test mode
172: [AC hex] Select the acceptance test mode
Dependency: Refer to: p9358, r9371
Refer to: C01799
Description: Displays the status of the acceptance test mode.
Values: 0: [00 hex] Acc_mode inactive
12: [0C hex] Acc_mode not possible due to POWER ON fault
13: [0D hex] Acc_mode not possible due to incorrect ID in p9370
15: [0F hex] Acc_mode not possible due to expired Acc_timer
172: [AC hex] Acc_mode active
Dependency: Refer to: p9358, p9370
Refer to: C01799
Description: Sets the delay time after which the pulses are safely canceled after a bus failure.
Dependency: Refer to: p9363
Notice: This parameter is overwritten by the copy function of the safety functions integrated in the drive.
The parameter is being prepared and is presently ineffective.
Note: A change only becomes effective after a POWER ON.
p9370 SI motion acceptance test mode (Motor Module) / SI Mtn acc_mod MM
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex 0000 hex
r9371 SI motion acceptance test status (Motor Module) / SI Mtn acc_stat MM
SERVO, VECTOR Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0000 hex 00AC hex -
p9380 SI motion pulse cancelation delay bus failure (Motor Module) / SI Mtn t to IL MM
SERVO, VECTOR Can be changed: C2 Calculated: - Access level: 4
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [µs] 800000.00 [µs] 0.00 [µs]