Description: Sets the offset voltage in the alpha direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the Motor Module.
Note: The value is pre-set during the rotating measurement.
Description: Sets the offset voltage in the beta direction; this compensates the offset voltages of the drive converter/inverter at
low speeds. The value is valid for the rated (nominal) pulse frequency of the Motor Module.
Note: The value is pre-set during the rotating measurement.
Description: Induction motor (ASM):
Displays the difference between the motor model flux angle and the transformation angle.
Permanent magnet synchronous motor (PEM):
Displays the difference between the motor model angle and the encoder angle.
Description: Displays the absolute value of the flux of the motor model.
p1774[0...n] Motor model, offset voltage compensation alpha / MotMod offs comp A
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]
p1775[0...n] Motor model, offset voltage compensation beta / MotMod offs comp B
VECTOR (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: Floating Point Dynamic index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
-5.000 [V] 5.000 [V] 0.000 [V]
r1778 Motor model flux angle difference / MotMod ang. diff.
SERVO, VECTOR
(n/M)
Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Expert list: 1
Min Max Factory setting
- [°] - [°] - [°]
r1779 Motor model absolute flux / MotMod abs flux
VECTOR (n/M) Can be changed: - Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]