Parameters
List of parameters
1-616
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
Description: Displays the smoothed actual value after the filter (PT1) of the technology controller
Description: Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency: Refer to: p2263
Description: Sets the time constant for the differentiation (D component) of the technology controller.
Note: p2274 = 0: Differentiation is disabled.
Description: Sets the proportional gain (P component) of the technology controller.
Note: p2280 = 0: The proportional gain is disabled.
p2265 Technology controller actual value filter time constant / Tec_ctrl act T
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.00 [s] 60.00 [s] 0.00 [s]
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r2273 CO: Technology controller error / Tec_ctrl error
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: 9_1 Unit selection: p0595
Not for motor type: - Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2274 Technology controller differentiation, time constant / Tec_ctrl T diff
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2280 Technology controller proportional gain / Tec_ctrl Kp
SERVO (Tech_ctrl),
VECTOR (Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Floating Point Dynamic index: - Func. diagram: 7958
P-Group: Technology Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0.000 1000.000 1.000