Siemens SINAMICS S Series - p1211 Automatic restart, start attempts; AR start attempts

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
List of parameters
1-338
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
p1210 = 1:
Faults that are present are automatically acknowledged. If new faults occur after a successful fault acknowledge-
ment, then these are also automatically acknowledged again. A minimum time of p1212 + 1s must expire between
a successful fault acknowledgement and a fault re-occurring if the signal ON/OFF1 (control word 1, bit 0) is at a
HIGH signal level. If the signal ON/OFF1 is at a LOW signal level, then the time between a successful fault
acknowledgement and a new fault must be at least 1s.
For p1210 = 1, fault F07320 is not generated if the acknowledgement attempt was not successful, for example, due
to frequently occurring faults.
Description: Sets the absolute number of start attempts for the automatic restart function when any faults are automatically
acknowledged (p1210 = 6).
Dependency: The setting of this parameter is always effective for p1210 = 6. For p1210 = 4, the parameter only has an influence
if an additional line phase failure (F6200) occurs at the start attempt.
Refer to: p1210, r1214
Refer to: F07320
Caution: A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Notice: After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
Note: A starting attempt starts immediately when a fault occurs. The restart attempt is considered to have been com-
pleted if the infeed is powered-up and an additional delay time of 1 s has expired.
As long as a fault is present, an acknowledge command is generated in the time intervals of p1212 / 2. When suc-
cessfully acknowledged, the start counter is decremented. If, after this, a fault re-occurs before a restart has been
completed, then acknowledgement starts again from the beginning.
Fault F07320 is output if, after several faults occur, the number of parameterized start attempts has been reached.
After a successful start attempt (i.e. a fault/error has no longer occurred up to the end of the power-up operation)
the start counter is again reset to the parameter value after 1 s. If faults re-occur, the parameterized number of start
attempts is again available.
At least one start attempt is always carried out.
After a line supply failure, acknowledgement is immediate and when the line supply returns, the system is powered-
up. If, between successfully acknowledging the line fault and the line supply returning, another fault occurs, then its
acknowledgement also causes the start counter to be decremented.
Description: Sets the absolute number of start attempts for the automatic restart function when any faults are automatically
acknowledged (p1210 = 6).
Dependency: The setting of this parameter is always effective for p1210 = 6. For p1210 = 4, the parameter only has an influence
if an additional undervoltage fault occurs at the start attempt.
Refer to: p1210, r1214
Refer to: F07320
Caution: A change is only accepted and made if the state "initialization" (r1214.0) and "wait for alarm" (r1214.1).
Notice: After fault F07320 occurs, the power-on command must be withdrawn and all of the faults acknowledged so that the
automatic restart function is re-activated.
p1211 Automatic restart, start attempts / AR start attempts
A_INF, B_INF,
S_INF
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 10 3
p1211 Automatic restart, start attempts / AR start attempts
SERVO, VECTOR Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dynamic index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
0 10 3