List of parameters
Parameters
1-695
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
Description: Sets the signal source for the negated enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3111
Refer to: F07862
p3111[0...n] BI: External fault 3, enable / Ext fault 3 enab
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 1
p3112 BI: External fault 3 enable negated / Ext flt 3 enab neg
CU_CX32, CU_LINK,
CU_S, DMC20,
TB30, TM15,
TM15DI_DO, TM17,
TM31, TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: - Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0
p3112[0...n] BI: External fault 3 enable negated / Ext flt 3 enab neg
A_INF, B_INF,
SERVO, S_INF,
TM41, VECTOR
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dynamic index: CDS, p0170 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - 0