Faults and Alarms
List of faults and alarms
3-1566
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
A07580 (F, N) Drive: No Sensor Module with matching component number
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: A Sensor Module with the component number specified in p0141 was not found.
Alarm value (r2124, interpret decimal):
Encoder data set involved (index of p0141).
Remedy: Correct parameter p0141.
Reaction upon F: OFF1 (IASC / DCBRAKE, NONE, OFF2, OFF3, STOP1, STOP2)
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
A07581 (F) Encoder 1: Position actual value preprocessing error
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: An error has occurred during the position actual value preprocessing.
Remedy: Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
Reaction upon F: OFF1 (OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
A07582 (F) Encoder 2: Position actual value preprocessing error
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: An error has occurred during the position actual value preprocessing.
Remedy: Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
Reaction upon F: OFF1 (OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
A07583 (F) Encoder 3: Position actual value preprocessing error
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: An error has occurred during the position actual value preprocessing.
Remedy: Check the encoder for the position actual value preprocessing.
See also: p2502 (LR encoder assignment)
Reaction upon F: OFF1 (OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
A07584 Encoder 1: Position setting value activated
Drive object: SERVO, VECTOR
Reaction: NONE
Acknowledge: NONE
Cause: The position actual value is set to the value received via CI: p2515while BI: p2514 = 1 signal. A possible system
deviation cannot be corrected.
Remedy: None necessary.
The alarm automatically disappears with BI: p2514 = 0 signal.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINAMICS S Series and is the answer not in the manual?

Siemens SINAMICS S Series Specifications

General IconGeneral
BrandSiemens
ModelSINAMICS S Series
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals